Current rating |
16A, 20A and 32A |
Voltage rating |
All regional Voltages, ±10% |
Type |
1-Phase/2-Pole |
Frequency |
50Hz and 60Hz, ±10% – Auto detection |
Transfer type |
Break-Before-Make zero current transfer by Thyristors / SCR |
Synchronous break time |
<1ms – asynchronous break time up to % cycle |
MTBF |
>800,000 hours |
Maintenance bypass |
Cradle with 3-position overlapping, no-break CAM switch |
Isolation |
Incoming sources isolator switches |
Display |
Bi-colour LED mimic decal with graphic OLED display and information interface |
Interface |
Preferred supply selection, Source transfer selection and Alarm cancel button |
Contact |
2 Self wetting transfer control inputs
5 Voltage free change-over status indicators, Form C |
Ethernet |
HTTP, SNMP, MODBUS TCP, Email & NTP |
Input options |
Fixed wiring to terminals up to 6mm2 cables via glands |
Output options |
Fixed wiring to terminals up to 6mm2 cables via glands |
Dimensions H x W x D |
1RU/19″ – 44 x 483 x 540mm |
Weight |
11kg |
Temperature |
0 – 45°C |
IP rating |
IP31 |
Detection |
Digital: <1ms |
Asynchronous break time |
0ms, 10ms, 50ms or Vt proportional, 0° to 180° |
Loading |
0 -100% @45°C ambient |
Device ratings |
150Arms, 1400V, 2kA 1 cycle |
Overload @40°C ambient |
63A for 30s 100A for 1s
225A for 0.1s 2kA for 1 cycle |
Fault current setting |
350% peak with load fault transfer inhibit |
Safe install environment |
20kA, 100A internally fused |
Protection |
100A fuses – BS88/FE100 |
Power factor |
No practical limit |
Max THDV |
10% – Max allowable source voltage distortion |
Crestfactor |
3.5:1 |
dV/dt max |
800V/ps |
Cooling |
Passive |
Humidity @40°C ambient |
5 – 95% non-condensing |
Regulatory approvals |
IEC 62310-1,2,3 – IEC 60950 – IEC 61000-6-1,2,3,4 – CE – RCM – UL Capable – RoHS |
Standard warranty |
24 months offsite repair or replacement policy |